Wire Size Calculator

A 20 A, 120 V copper circuit running 100 ft one way needs 12 AWG for ampacity, but 8 AWG to keep voltage drop at or under 3% (2.59%). Voltage drop = 2 × I × R × L ÷ 1000, with R from NEC Chapter 9 Table 8.

NEC 2023 Table 310.16 and Chapter 9 Table 8. Not a design approval: the final call belongs to your local AHJ and a licensed electrician.

Did this solve your problem?
Prefer us on Google

How to use

  1. Enter the load current, the circuit voltage, and pick single phase (also use this for DC) or three phase.
  2. Enter the one-way length from the panel to the load and the voltage drop you allow. 3% for a branch circuit and 5% for feeder plus branch circuit is the usual target from the NEC informational notes.
  3. Pick copper or aluminum, the insulation and terminal ratings, and whether the load is continuous. The result is the larger of the ampacity size and the voltage drop size.

How it works

Ampacity: the same check as the wire ampacity chart. NEC Table 310.16 at 30°C, up to three current-carrying conductors, the terminal temperature limit of 110.14(C), 125% for continuous loads and the 240.4(D) small conductor limits.

Voltage drop for single phase or DC is VD = 2 × I × R × L ÷ 1000, and for three phase VD = √3 × I × R × L ÷ 1000, where I is the load in amps, L the one-way length in feet and R the DC resistance in ohms per 1000 ft at 75°C from NEC Chapter 9 Table 8 (stranded, uncoated copper or aluminum).

The drop percentage is VD ÷ voltage × 100. Table 8 is DC resistance, so for large conductors on AC (about 1/0 and up) the real drop is somewhat higher because of reactance. Table 9 gives AC impedance for that case.

AWG wire gauge chart

Solid diameter is from the AWG definition, d = 0.005 × 92^((36 − n) ÷ 39) inches. Stranded diameter, area and resistance at 75°C are from NEC Chapter 9 Table 8.

SizeCircular milsArea mm²Solid diameter inStranded diameter inCu Ω/kftAl Ω/kft
14 AWG41102.080.0641 (1.63 mm)0.0733.145.17
12 AWG65303.310.0808 (2.05 mm)0.0921.983.25
10 AWG103805.2610.1019 (2.59 mm)0.1161.242.04
8 AWG165108.3670.1285 (3.26 mm)0.1460.7781.28
6 AWG2624013.30.1620 (4.12 mm)0.1840.4910.808
4 AWG4174021.150.2043 (5.19 mm)0.2320.3080.508
3 AWG5262026.670.2294 (5.83 mm)0.2600.2450.403
2 AWG6636033.620.2576 (6.54 mm)0.2920.1940.319
1 AWG8369042.410.2893 (7.35 mm)0.3320.1540.253
1/0 AWG10560053.490.3249 (8.25 mm)0.3720.1220.201
2/0 AWG13310067.430.3648 (9.27 mm)0.4180.09670.159
3/0 AWG16780085.010.4096 (10.40 mm)0.4700.07660.126
4/0 AWG211600107.20.4600 (11.68 mm)0.5280.06080.1
250 kcmil2500001270.5000 (12.70 mm)0.5750.05150.0847
300 kcmil3000001520.5477 (13.91 mm)0.6300.04290.0707
350 kcmil3500001770.5916 (15.03 mm)0.6810.03670.0605
400 kcmil4000002030.6325 (16.06 mm)0.7280.03210.0529
500 kcmil5000002530.7071 (17.96 mm)0.8130.02580.0424
600 kcmil6000003040.7746 (19.67 mm)0.8930.02140.0353
700 kcmil7000003550.8367 (21.25 mm)0.9640.01840.0303
750 kcmil7500003800.8660 (22.00 mm)0.9980.01710.0282
800 kcmil8000004050.8944 (22.72 mm)1.0300.01610.0265
900 kcmil9000004560.9487 (24.10 mm)1.0940.01430.0235
1000 kcmil10000005071.0000 (25.40 mm)1.1520.01290.0212
1250 kcmil12500006331.1180 (28.40 mm)1.2890.01030.0169
1500 kcmil15000007601.2247 (31.11 mm)1.4120.008580.0141
1750 kcmil17500008871.3229 (33.60 mm)1.5260.007350.0121
2000 kcmil200000010131.4142 (35.92 mm)1.6320.006430.0106

Voltage drop examples, 120 V copper

Load and wire50 ft100 ft150 ft
15 A, 14 AWG3.92%7.85%11.78%
20 A, 12 AWG3.30%6.60%9.90%
30 A, 10 AWG3.10%6.20%9.30%
40 A, 8 AWG2.59%5.19%7.78%

Before you rely on the result

  • Ampacity values follow NEC 2023 (same as 2020). Resistance values are the same in 2017 to 2023.
  • Ambient temperature and more than three conductors are not adjusted here. Use the wire ampacity chart for those.
  • The final decision belongs to your local AHJ and a licensed electrician.

FAQ

Is a 3% voltage drop required by code?

No. The 3% and 5% figures are in informational notes to 210.19(A) and 215.2(A), so they are recommendations. Some equipment, such as fire pumps or sensitive electronics, has its own mandatory limits, and some local codes adopt the limit.

Should I enter one-way or round-trip length?

One way, from the source to the load. The factor 2 (or √3 for three phase) in the formula accounts for the return path.

Why does a longer run need a bigger wire than the ampacity table says?

Ampacity is about heat in the conductor. Voltage drop is about resistance over distance. A long run can be safe thermally but still deliver too little voltage, so the tool picks the larger of the two sizes.

What resistance values are used?

NEC Chapter 9 Table 8, DC resistance at 75°C in ohms per 1000 ft for stranded conductors: for example 3.14 for 14 AWG copper, 1.98 for 12 AWG and 1.24 for 10 AWG. These values are unchanged in the 2017, 2020 and 2023 editions.

Does it work for 12 V or 24 V DC?

Yes, pick single phase and enter the DC voltage. Low-voltage runs are usually limited by voltage drop rather than ampacity.

Who makes the final call?

This is a sizing check. The final decision belongs to your local AHJ and a licensed electrician, who will also look at conditions this tool does not model, such as ambient temperature, bundling and equipment listings.