Wire Ampacity Chart and Calculator (NEC 310.16)

Under NEC Table 310.16 (2023), a 40 A load on copper with 75°C terminals needs 8 AWG, 60 A needs 6 AWG and 100 A needs 3 AWG. Aluminum at 200 A needs 250 kcmil. These assume 30°C ambient and no more than 3 current-carrying conductors.

Did this solve your problem?
Prefer us on Google

How to use

  1. Enter the load current in amps and pick copper or aluminum.
  2. Pick the insulation temperature rating of the wire (THHN and THWN-2 are 90°C, NM-B cable is limited to the 60°C column) and the temperature rating of the terminals on the breaker and equipment. Auto follows NEC 110.14(C): 60°C for circuits up to 100 A, 75°C above.
  3. Enter the ambient temperature and the number of current-carrying conductors in the raceway or cable. Tick continuous load if the current runs for 3 hours or more, so 125% is applied.

How it works

The starting value is the ampacity from NEC Table 310.16 in the column of the insulation rating (30°C ambient, not more than three current-carrying conductors in a raceway, cable or earth).

That value is multiplied by the ambient temperature correction factor from Table 310.15(B)(1)(1) and the adjustment factor for more than three current-carrying conductors from Table 310.15(C)(1) (80% for 4 to 6, 70% for 7 to 9, 50% for 10 to 20 and so on). The adjusted ampacity must be at least the load.

The terminal check uses the column of the terminal rating without corrections, and must be at least the load (125% of it for a continuous load). Copper 14, 12 and 10 AWG are also limited by 240.4(D) to 15, 20 and 30 A overcurrent protection (aluminum 12 and 10 AWG to 15 and 25 A). The smallest size that passes all checks is shown.

NEC Table 310.16 ampacity chart

Amps at 30°C (86°F) ambient, not more than three current-carrying conductors in a raceway, cable or earth. Aluminum includes copper-clad aluminum. Sizes marked by 240.4(D) have a lower breaker limit: copper 14, 12, 10 AWG at 15, 20, 30 A, aluminum 12, 10 AWG at 15, 25 A.

SizeCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
14 AWG152025---
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
800 kcmil410490555330395445
900 kcmil435520585355425480
1000 kcmil455545615375445500
1250 kcmil495590665405485545
1500 kcmil525625705435520585
1750 kcmil545650735455545615
2000 kcmil555665750470560630

Wire size by breaker

Minimum size for a non-continuous load equal to the breaker rating, 30°C ambient, up to 3 current-carrying conductors.

BreakerCu, 60°C terminalsCu, 75°C terminalsAl, 60°C terminalsAl, 75°C terminals
15 A14 AWG14 AWG12 AWG12 AWG
20 A12 AWG12 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG8 AWG
40 A8 AWG8 AWG6 AWG8 AWG
50 A6 AWG8 AWG4 AWG6 AWG
60 A4 AWG6 AWG3 AWG4 AWG
70 A4 AWG4 AWG2 AWG3 AWG
100 A1 AWG3 AWG1/0 AWG1 AWG
125 A1/0 AWG1 AWG3/0 AWG2/0 AWG
150 A3/0 AWG1/0 AWG4/0 AWG3/0 AWG
200 A250 kcmil3/0 AWG350 kcmil250 kcmil

Ambient temperature correction, Table 310.15(B)(1)(1)

Ambient60°C75°C90°C
≤ 10 °C (≤ 50 °F)1.291.201.15
11-15 °C (51-59 °F)1.221.151.12
16-20 °C (60-68 °F)1.151.111.08
21-25 °C (69-77 °F)1.081.051.04
26-30 °C (78-86 °F)1.001.001.00
31-35 °C (87-95 °F)0.910.940.96
36-40 °C (96-104 °F)0.820.880.91
41-45 °C (105-113 °F)0.710.820.87
46-50 °C (114-122 °F)0.580.750.82
51-55 °C (123-131 °F)0.410.670.76
56-60 °C (132-140 °F)-0.580.71
61-65 °C (141-149 °F)-0.470.65
66-70 °C (150-158 °F)-0.330.58
71-75 °C (159-167 °F)--0.50
76-80 °C (168-176 °F)--0.41
81-85 °C (177-185 °F)--0.29

More than three conductors, Table 310.15(C)(1)

Current-carrying conductorsPercent of value
4-680%
7-970%
10-2050%
21-3045%
31-4040%
41+35%

Before you rely on the result

  • Values follow NEC 2023 (same as 2020). Local codes may amend them.
  • Voltage drop is not checked here. Use the wire size calculator for long runs.
  • The final decision belongs to your local AHJ and a licensed electrician.

FAQ

Which NEC edition is this based on?

NEC 2023 (NFPA 70). Table 310.16 and its correction tables have the same values in the 2020 edition. In 2017 the same table was numbered 310.15(B)(16). If your jurisdiction has adopted the 2026 NEC, check the values against your code book.

Why does 12 AWG copper show 25 A at 75°C but only allow a 20 A breaker?

NEC 240.4(D) limits the overcurrent protection of small conductors regardless of the table: 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A. The calculator applies that limit, so a 25 A load moves up to 10 AWG.

Why use the 90°C column if my breaker is rated 75°C?

NEC allows you to start corrections and adjustments from the 90°C column of 90°C wire, but the final ampacity cannot exceed the column of the lowest-rated termination. The tool checks both: the derated 90°C value against the load, and the unadjusted terminal column against the load.

What counts as a current-carrying conductor?

Ungrounded (hot) conductors carry current. A neutral that carries only the unbalanced current of a 3-wire single-phase or 4-wire three-phase circuit is not counted, and equipment grounding conductors are never counted. On a 4-wire wye circuit with mostly nonlinear loads, the neutral counts.

Does this apply to dwelling services?

No adjustment for 310.12 is made. For a 120/240 V dwelling service or main feeder, 310.12 allows the conductor to be sized at 83% of the service rating, which this calculator does not apply.

Who makes the final call?

Use the result as a check, not as a design approval. Local amendments, equipment listings and installation details matter, so the final decision belongs to your local AHJ (authority having jurisdiction) and a licensed electrician.