Wire Ampacity Chart and Calculator (NEC 310.16)
Under NEC Table 310.16 (2023), a 40 A load on copper with 75°C terminals needs 8 AWG, 60 A needs 6 AWG and 100 A needs 3 AWG. Aluminum at 200 A needs 250 kcmil. These assume 30°C ambient and no more than 3 current-carrying conductors.
How to use
- Enter the load current in amps and pick copper or aluminum.
- Pick the insulation temperature rating of the wire (THHN and THWN-2 are 90°C, NM-B cable is limited to the 60°C column) and the temperature rating of the terminals on the breaker and equipment. Auto follows NEC 110.14(C): 60°C for circuits up to 100 A, 75°C above.
- Enter the ambient temperature and the number of current-carrying conductors in the raceway or cable. Tick continuous load if the current runs for 3 hours or more, so 125% is applied.
How it works
The starting value is the ampacity from NEC Table 310.16 in the column of the insulation rating (30°C ambient, not more than three current-carrying conductors in a raceway, cable or earth).
That value is multiplied by the ambient temperature correction factor from Table 310.15(B)(1)(1) and the adjustment factor for more than three current-carrying conductors from Table 310.15(C)(1) (80% for 4 to 6, 70% for 7 to 9, 50% for 10 to 20 and so on). The adjusted ampacity must be at least the load.
The terminal check uses the column of the terminal rating without corrections, and must be at least the load (125% of it for a continuous load). Copper 14, 12 and 10 AWG are also limited by 240.4(D) to 15, 20 and 30 A overcurrent protection (aluminum 12 and 10 AWG to 15 and 25 A). The smallest size that passes all checks is shown.
NEC Table 310.16 ampacity chart
Amps at 30°C (86°F) ambient, not more than three current-carrying conductors in a raceway, cable or earth. Aluminum includes copper-clad aluminum. Sizes marked by 240.4(D) have a lower breaker limit: copper 14, 12, 10 AWG at 15, 20, 30 A, aluminum 12, 10 AWG at 15, 25 A.
| Size | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | - | - | - |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
| 600 kcmil | 350 | 420 | 475 | 285 | 340 | 385 |
| 700 kcmil | 385 | 460 | 520 | 315 | 375 | 425 |
| 750 kcmil | 400 | 475 | 535 | 320 | 385 | 435 |
| 800 kcmil | 410 | 490 | 555 | 330 | 395 | 445 |
| 900 kcmil | 435 | 520 | 585 | 355 | 425 | 480 |
| 1000 kcmil | 455 | 545 | 615 | 375 | 445 | 500 |
| 1250 kcmil | 495 | 590 | 665 | 405 | 485 | 545 |
| 1500 kcmil | 525 | 625 | 705 | 435 | 520 | 585 |
| 1750 kcmil | 545 | 650 | 735 | 455 | 545 | 615 |
| 2000 kcmil | 555 | 665 | 750 | 470 | 560 | 630 |
Wire size by breaker
Minimum size for a non-continuous load equal to the breaker rating, 30°C ambient, up to 3 current-carrying conductors.
| Breaker | Cu, 60°C terminals | Cu, 75°C terminals | Al, 60°C terminals | Al, 75°C terminals |
|---|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 6 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG | 4 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 3 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 2 AWG | 3 AWG |
| 100 A | 1 AWG | 3 AWG | 1/0 AWG | 1 AWG |
| 125 A | 1/0 AWG | 1 AWG | 3/0 AWG | 2/0 AWG |
| 150 A | 3/0 AWG | 1/0 AWG | 4/0 AWG | 3/0 AWG |
| 200 A | 250 kcmil | 3/0 AWG | 350 kcmil | 250 kcmil |
Ambient temperature correction, Table 310.15(B)(1)(1)
| Ambient | 60°C | 75°C | 90°C |
|---|---|---|---|
| ≤ 10 °C (≤ 50 °F) | 1.29 | 1.20 | 1.15 |
| 11-15 °C (51-59 °F) | 1.22 | 1.15 | 1.12 |
| 16-20 °C (60-68 °F) | 1.15 | 1.11 | 1.08 |
| 21-25 °C (69-77 °F) | 1.08 | 1.05 | 1.04 |
| 26-30 °C (78-86 °F) | 1.00 | 1.00 | 1.00 |
| 31-35 °C (87-95 °F) | 0.91 | 0.94 | 0.96 |
| 36-40 °C (96-104 °F) | 0.82 | 0.88 | 0.91 |
| 41-45 °C (105-113 °F) | 0.71 | 0.82 | 0.87 |
| 46-50 °C (114-122 °F) | 0.58 | 0.75 | 0.82 |
| 51-55 °C (123-131 °F) | 0.41 | 0.67 | 0.76 |
| 56-60 °C (132-140 °F) | - | 0.58 | 0.71 |
| 61-65 °C (141-149 °F) | - | 0.47 | 0.65 |
| 66-70 °C (150-158 °F) | - | 0.33 | 0.58 |
| 71-75 °C (159-167 °F) | - | - | 0.50 |
| 76-80 °C (168-176 °F) | - | - | 0.41 |
| 81-85 °C (177-185 °F) | - | - | 0.29 |
More than three conductors, Table 310.15(C)(1)
| Current-carrying conductors | Percent of value |
|---|---|
| 4-6 | 80% |
| 7-9 | 70% |
| 10-20 | 50% |
| 21-30 | 45% |
| 31-40 | 40% |
| 41+ | 35% |
Before you rely on the result
- Values follow NEC 2023 (same as 2020). Local codes may amend them.
- Voltage drop is not checked here. Use the wire size calculator for long runs.
- The final decision belongs to your local AHJ and a licensed electrician.
FAQ
Which NEC edition is this based on?
NEC 2023 (NFPA 70). Table 310.16 and its correction tables have the same values in the 2020 edition. In 2017 the same table was numbered 310.15(B)(16). If your jurisdiction has adopted the 2026 NEC, check the values against your code book.
Why does 12 AWG copper show 25 A at 75°C but only allow a 20 A breaker?
NEC 240.4(D) limits the overcurrent protection of small conductors regardless of the table: 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A. The calculator applies that limit, so a 25 A load moves up to 10 AWG.
Why use the 90°C column if my breaker is rated 75°C?
NEC allows you to start corrections and adjustments from the 90°C column of 90°C wire, but the final ampacity cannot exceed the column of the lowest-rated termination. The tool checks both: the derated 90°C value against the load, and the unadjusted terminal column against the load.
What counts as a current-carrying conductor?
Ungrounded (hot) conductors carry current. A neutral that carries only the unbalanced current of a 3-wire single-phase or 4-wire three-phase circuit is not counted, and equipment grounding conductors are never counted. On a 4-wire wye circuit with mostly nonlinear loads, the neutral counts.
Does this apply to dwelling services?
No adjustment for 310.12 is made. For a 120/240 V dwelling service or main feeder, 310.12 allows the conductor to be sized at 83% of the service rating, which this calculator does not apply.
Who makes the final call?
Use the result as a check, not as a design approval. Local amendments, equipment listings and installation details matter, so the final decision belongs to your local AHJ (authority having jurisdiction) and a licensed electrician.