Refrigerant PT Chart and Superheat Calculator

Superheat = suction line temperature − dew-point saturation temperature at suction pressure; subcooling = bubble-point saturation temperature at liquid pressure − liquid line temperature. For R-410A at 118 psig suction the dew point is 39.8 °F, so a 52 °F suction line has 12.2 °F superheat; at 365 psig the bubble point is 109.7 °F, so a 100 °F liquid line has 9.7 °F subcooling.

Reference only. Follow the equipment maker's charging chart and local refrigerant handling rules.

Did this solve your problem?
Prefer us on Google

How to use

  1. Pick the refrigerant. Blends (R-410A, R-454B, R-404A) have two saturation temperatures at the same pressure: the bubble point (liquid) and the dew point (vapor).
  2. Choose gauge units (psig, kPa or bar) and °F or °C. Switching converts the numbers already typed.
  3. For superheat, enter the suction pressure and the suction line temperature measured near the evaporator outlet or the outdoor unit. For subcooling, enter the liquid line pressure and the liquid line temperature. You can fill either pair or both.
  4. Read the superheat and subcooling, the saturation temperatures used, and the full PT chart below for the chosen refrigerant and units.

How it works

Superheat = suction line temperature − dew-point temperature at the suction pressure. Subcooling = bubble-point temperature at the liquid pressure − liquid line temperature. For blends with glide, using the bubble point for superheat or the dew point for subcooling gives the wrong answer.

Gauge to absolute: psia = psig + 14.696. kPa and bar inputs are gauge values too (1 psi = 6.894757 kPa). Between the 5 °F rows the tool interpolates ln(pressure) linearly in temperature.

Data and cross-checks: the tables are copied from manufacturer property tables built on NIST REFPROP: Arkema Forane ENG tables for R-410A, R-22 and R-404A, Chemours Freon 134a ENG and Chemours Opteon XL41 (R-454B) ENG. R-32 comes from the Hudson Technologies PT chart. Every row was compared with a second source: Chemours SI tables for R-410A and R-404A (within 0.6% and 1.2% at −40 °F), Arkema SI for R-134a (0.12%), the Hudson chart for R-22 and R-454B bubble pressures (within 0.6 psi), and the CoolProp equation of state for R-22, R-134a and R-32 (within 0.14%).

Typical targets (check the equipment label and the manufacturer's charging chart): TXV and EEV systems are often charged to 8 to 12 °F subcooling; fixed-orifice systems are charged by a target superheat that depends on indoor wet-bulb and outdoor temperature.

This is a reference tool. Follow the equipment manufacturer's charging procedure, EPA Section 608 rules and safety practice for A2L refrigerants such as R-32 and R-454B.

Saturation pressures at a glance

Refrigerant40 °F dew (evaporator)100 °F bubble (condenser)Glide at 100 °F
R-410A118.4 psig (8.16 bar)318.5 psig (21.96 bar)0.2 °F (0.1 K)
R-2268.6 psig (4.73 bar)195.9 psig (13.51 bar)0
R-32121.0 psig (8.34 bar)325.7 psig (22.46 bar)0
R-454B107.0 psig (7.38 bar)300.8 psig (20.74 bar)2.3 °F (1.3 K)
R-134a35.1 psig (2.42 bar)124.3 psig (8.57 bar)0
R-404A85.4 psig (5.89 bar)236.8 psig (16.33 bar)0.6 °F (0.4 K)

Sources: Arkema Forane 410A thermodynamic properties · Arkema Forane 22 thermodynamic properties · Arkema Forane 404A thermodynamic properties · Chemours Freon 134a thermodynamic properties · Chemours Opteon XL41 (R-454B) properties · Hudson Technologies R-32 PT chart · Chemours Freon 410A properties (SI)Last reviewed 2026-10-21

FAQ

How do you calculate superheat?

Read the suction pressure, find the saturation temperature for it on the PT chart (the dew point for blends), and subtract it from the suction line temperature. R-410A at 118 psig saturates at about 40 °F, so a 52 °F suction line means 12 °F superheat.

How do you calculate subcooling?

Read the liquid line pressure, find its saturation temperature (the bubble point for blends) and subtract the liquid line temperature. R-410A at 365 psig saturates at about 110 °F, so a 100 °F liquid line means about 10 °F subcooling.

What is the difference between bubble and dew point?

A blend boils over a temperature range. The bubble point is where liquid starts to boil and the dew point is where the last liquid has boiled. R-454B has about 1.5 K (2 to 3 °F) of glide; R-410A has almost none.

What should R-410A pressures be?

It depends on load and outdoor temperature. With a 40 °F evaporator the suction is about 118 psig, and with a 100 °F condensing temperature the head is about 318 psig. Compare with the unit's charging chart rather than a single number.

Is R-454B a drop-in for R-410A?

No. R-454B is an A2L (mildly flammable) refrigerant used in new equipment designed for it. Its pressures are a little lower than R-410A at the same temperature. Never mix refrigerants or top up one with another.