Conduit Fill Calculator

Conduit fill = total wire area (NEC Chapter 9 Table 5) ÷ conduit area (Table 4), max 40% for 3 or more wires. 1/2 in EMT holds 9 12 AWG THHN and 3/4 in holds 16. Three 4/0 THHN plus a 4 AWG ground (1.0535 in²) need 2 in EMT.

Wire group 1
Wire group 2
Wire group 3

NEC 2023 Chapter 9 Tables 1, 4 and 5. Not a design approval: the final call belongs to your local AHJ and a licensed electrician.

Did this solve your problem?
Prefer us on Google

How to use

  1. Pick the conduit or tubing type: EMT, IMC, RMC, PVC Schedule 40 or 80, FMC or LFMC.
  2. For each group of wires enter the count, the insulation type and the size. Include the equipment grounding conductor, because it counts for fill.
  3. Tick the nipple box if the raceway is a nipple of 24 in (600 mm) or less between boxes or enclosures, which may be filled to 60%.

How it works

Each wire area comes from NEC Chapter 9 Table 5 (with insulation), for example 12 AWG THHN 0.0133 in² and 12 AWG XHHW 0.0181 in². The areas are added up.

The allowed fill from Table 1 is 53% of the conduit area for one wire, 31% for two and 40% for three or more. Conduit areas are the 100% values from Table 4 for each raceway type and trade size.

The smallest trade size whose allowed area is at least the total wire area is shown. For tables of a single wire size, Chapter 9 Note 7 lets the count round up when the decimal is 0.8 or more, which is how the Annex C tables (and the max count table below) are built.

Max THHN wires in EMT (same size)

Built with the same method as NEC Annex C Table C.1: 40% fill and the Note 7 round-up.

Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in
14 AWG1222356184138
12 AWG916264561101
10 AWG51016283863
8 AWG369162236
6 AWG147121626
4 AWG12471016
3 AWG1136813
2 AWG1135711
1 AWG111458
1/0 AWG011347

Max THHN wires in PVC Schedule 40 (same size)

Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in
14 AWG1121346082135
12 AWG81525435999
10 AWG5915273762
8 AWG359162136
6 AWG146111526
4 AWG1147916
3 AWG1136813
2 AWG1135711
1 AWG011358
1/0 AWG011347

Conduit internal area, Chapter 9 Table 4

Total area at 100% in in², with 40% in brackets (computed from the 100% value, which can differ from the printed 40% column by 0.001).

Trade sizeEMTIMCRMCPVC 40PVC 80FMCLFMC
3/8 in-----0.116 (0.046)0.192 (0.077)
1/2 in0.304 (0.122)0.342 (0.137)0.314 (0.126)0.285 (0.114)0.217 (0.087)0.317 (0.127)0.314 (0.126)
3/4 in0.533 (0.213)0.586 (0.234)0.549 (0.220)0.508 (0.203)0.409 (0.164)0.533 (0.213)0.541 (0.216)
1 in0.864 (0.346)0.959 (0.384)0.887 (0.355)0.832 (0.333)0.688 (0.275)0.817 (0.327)0.873 (0.349)
1-1/4 in1.496 (0.598)1.647 (0.659)1.526 (0.610)1.453 (0.581)1.237 (0.495)1.277 (0.511)1.528 (0.611)
1-1/2 in2.036 (0.814)2.225 (0.890)2.071 (0.828)1.986 (0.794)1.711 (0.684)1.858 (0.743)1.981 (0.792)
2 in3.356 (1.342)3.630 (1.452)3.408 (1.363)3.291 (1.316)2.874 (1.150)3.269 (1.308)3.246 (1.298)
2-1/2 in5.858 (2.343)5.135 (2.054)4.866 (1.946)4.695 (1.878)4.119 (1.648)4.909 (1.964)4.881 (1.952)
3 in8.846 (3.538)7.922 (3.169)7.499 (3.000)7.268 (2.907)6.442 (2.577)7.069 (2.828)7.475 (2.990)
3-1/2 in11.545 (4.618)10.584 (4.234)10.010 (4.004)9.737 (3.895)8.688 (3.475)9.621 (3.848)9.731 (3.892)
4 in14.753 (5.901)13.631 (5.452)12.882 (5.153)12.554 (5.022)11.258 (4.503)12.566 (5.026)12.692 (5.077)
5 in--20.212 (8.085)19.761 (7.904)17.855 (7.142)--
6 in--29.158 (11.663)28.567 (11.427)25.598 (10.239)--

Before you rely on the result

  • Values follow NEC 2023 Chapter 9 (same as 2017 and 2020).
  • Compact conductors (Table 5A) and cables are not covered.
  • The final decision belongs to your local AHJ and a licensed electrician.

FAQ

Which NEC edition is this?

NEC 2023. The Chapter 9 Table 1, 4 and 5 values used here are the same in the 2017 and 2020 editions. If you are on the 2026 NEC, check against your code book.

Does the ground wire count?

Yes. Equipment grounding and bonding conductors, insulated or bare, count toward conduit fill (Chapter 9 Note 3). They do not count as current-carrying conductors for ampacity adjustment.

Why is PVC Schedule 80 bigger than EMT for the same wires?

Schedule 80 has a thicker wall, so its inside area is smaller. 1 in Schedule 80 has 0.688 in² against 0.864 in² for 1 in EMT.

What about cables like NM-B or MC in conduit?

A multiconductor cable counts as one conductor, using its overall diameter. For an oval cable, use the major diameter as a circle. This tool covers individual THHN and XHHW conductors only.

Is 40% the only limit?

No. Fill only sets how much fits. The ampacity adjustment for more than three current-carrying conductors and the pulling tension and jam ratio for three wires can matter more. Very full raceways are hard to pull even when legal.

Who makes the final call?

This is a planning check. The final decision belongs to your local AHJ and a licensed electrician.