Box Fill Calculator (NEC 314.16)
Under NEC 314.16, two 14/2 cables with ground, internal clamps and one switch count as 8 volumes of 2.00 in³ = 16 in³, so a 3 × 2 × 3-1/2 in device box (18.0 in³) is enough and a 3 × 2 × 2-1/2 (12.5 in³) is not. 12 AWG is 2.25 in³ per volume.
How to use
- Pick a standard metal box from Table 314.16(A), or choose the custom option and enter the volume marked on the box (plastic boxes are marked by the maker). Add the marked volume of any plaster ring, extension ring or raised cover.
- Enter how many insulated conductors of each size enter the box or pass through it. Wires that stay entirely inside the box, such as pigtails, are not counted.
- Enter the number of devices (each yoke or strap), the grounds and fittings, and tick internal clamps if the box has any. The result compares the required volume with the box.
How it works
Each conductor that starts outside the box and ends or is spliced inside counts once, and each conductor that passes through unbroken counts once, using the volume from Table 314.16(B): 18 AWG 1.50, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00 and 6 AWG 5.00 in³.
One or more internal cable clamps count as one volume of the largest conductor in the box. Each type of support fitting (fixture stud, hickey) counts as one volume of the largest conductor. Each device yoke counts as two volumes of the largest conductor connected to that device.
Equipment grounding conductors: up to four count as one volume of the largest one, and each additional one adds a quarter volume (NEC 2020 and later). The sum is compared with the box volume plus any ring or extension volume.
Volume per conductor, Table 314.16(B)
| Conductor size | in³ per conductor |
|---|---|
| 18 AWG | 1.50 |
| 16 AWG | 1.75 |
| 14 AWG | 2.00 |
| 12 AWG | 2.25 |
| 10 AWG | 2.50 |
| 8 AWG | 3.00 |
| 6 AWG | 5.00 |
Standard metal boxes, Table 314.16(A)
Minimum volume in in³ and the maximum number of same-size conductors when nothing else is in the box.
| Box | in³ | 18 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
|---|---|---|---|---|---|---|---|---|
| Round/octagonal 4 × 1-1/4 in | 12.5 | 8 | 7 | 6 | 5 | 5 | 4 | 2 |
| Round/octagonal 4 × 1-1/2 in | 15.5 | 10 | 8 | 7 | 6 | 6 | 5 | 3 |
| Round/octagonal 4 × 2-1/8 in | 21.5 | 14 | 12 | 10 | 9 | 8 | 7 | 4 |
| Square 4 × 1-1/4 in | 18.0 | 12 | 10 | 9 | 8 | 7 | 6 | 3 |
| Square 4 × 1-1/2 in | 21.0 | 14 | 12 | 10 | 9 | 8 | 7 | 4 |
| Square 4 × 2-1/8 in | 30.3 | 20 | 17 | 15 | 13 | 12 | 10 | 6 |
| Square 4-11/16 × 1-1/2 in | 29.5 | 19 | 16 | 14 | 13 | 11 | 9 | 5 |
| Square 4-11/16 × 2-1/8 in | 42.0 | 28 | 24 | 21 | 18 | 16 | 14 | 8 |
| Device 3 × 2 × 2 in | 10.0 | 6 | 5 | 5 | 4 | 4 | 3 | 2 |
| Device 3 × 2 × 2-1/2 in | 12.5 | 8 | 7 | 6 | 5 | 5 | 4 | 2 |
| Device 3 × 2 × 2-3/4 in | 14.0 | 9 | 8 | 7 | 6 | 5 | 4 | 2 |
| Device 3 × 2 × 3-1/2 in | 18.0 | 12 | 10 | 9 | 8 | 7 | 6 | 3 |
| Utility (handy) 4 × 2-1/8 × 1-7/8 in | 13.0 | 8 | 7 | 6 | 5 | 5 | 4 | 2 |
| Utility (handy) 4 × 2-1/8 × 2-1/8 in | 14.5 | 9 | 8 | 7 | 6 | 5 | 4 | 2 |
Before you rely on the result
- Values follow NEC 2023 314.16, with the 2020 rule for grounds.
- Fixture wires under a domed canopy and other exceptions are not modeled.
- The final decision belongs to your local AHJ and a licensed electrician.
FAQ
Which NEC edition is this?
NEC 2023. The quarter volume for each ground beyond four was added in the 2020 NEC; under 2017 all grounds together counted as one volume. Check the 2026 edition against your code book if it applies to you.
Do wire nuts or pigtails count?
No. Wire connectors are not counted, and a conductor that does not leave the box, such as a pigtail to a device, is not counted either.
Does a looped wire count twice?
An unbroken conductor of at least twice the minimum free length (12 in or more) that is looped or coiled counts twice. A straight unbroken pass-through counts once. Enter a looped wire as two conductors.
What about a wide device like a GFCI?
Each yoke counts as two volumes. A device or equipment wider than a single 2 in device box counts two volumes for each gang it needs. Enter it as that many devices.
What if my box volume is not in the table?
Boxes of 100 in³ or less that are not in Table 314.16(A), including nonmetallic boxes, must be durably marked with their volume. Use the custom option and enter that marked value.
Who makes the final call?
This is a check, not an approval. The final decision belongs to your local AHJ and a licensed electrician.